Roof Space Condensation: Fix the Ceiling, Not Just the Vents

Jon Davies

Jon Davies

September 20,2026


Condensation in roof spaces is becoming more common, and ventilation alone isn't enough to address it. This article explains why managing internal moisture at the source, along with airtight construction and Above Sheathing Ventilation (ASV), offers the most effective way to reduce condensation risk in modern New Zealand roofs.

The recent article ‘The increasing problem of condensation and how to manage it’ in MRM SCOPE 117 exposes again the issue of moisture in roof spaces. It once was the domain of roofs to keep water out. Now they must keep water out and not trap moisture in. It doesn’t sound hard, but it is.

Moisture Leaking Up Is the Real Cause

At Pro Clima we take a different view on the ‘condensation in roof space’ problem. We all know that if we prevent problems from occurring, we don’t need to deal with their consequences. You can use whatever analogy you prefer — bike helmets to prevent head injury, fence at the top of the cliff… Now to be accurate, we can’t prevent 100% of the risk of roof space condensation, but it is certainly possible to prevent most of the moisture from inside a building from getting into the attic. I think it really is that simple. Airborne moisture leaking upwards from the house into the roof space is the cause of most of the problem.

Airtightness Isn't the Problem - It's Part of the Solution

So you can aim the blame at ‘more airtight houses’, but airtightness isn’t the problem, it is part of the solution!

  • Lack of ventilation of internally generated moisture is the first problem.

  • The second problem is the leakage into roof spaces: those roof spaces get colder and colder the more insulation we put into the roof, that’s physics at work, the colder the surface temperature of the trusses, the roof underlay and the roof cladding, the more moisture is going to condense. If that doesn’t dry fairly quickly, you’ll end up with mould, not just some pesky condensation.

  • Concrete slabs are another major contributor of moisture with condensation visibly forming on the underside of the roof underlay during construction. The amount of moisture that has to dry out from a concrete slab after it is poured is huge. A lack of ventilation during this drying time (roof is on, windows are closed overnight, cold roof is condensing moisture from below) shows up clearly. Normal thickness slabs (100mm deep) take up to three years to dry. In my books, that’s at least two years after carpet and people were installed. If three years sounds excessive, by a loose comparison, moisture models for heavy concrete buildings commonly use a 10-year period to predict drying.

21 Chimneys: A Lesson in Building Physics

20 years ago I was a regular contributor to an industry magazine. One unpublished article was entitled ’21 Chimneys’. It was never published, as I think it was a bit too political at the time (for the magazine). 21 chimneys referenced the 21 holes I cut into the ceilings for new downlights during our renovation. It was a typical renovation, mostly paint, some fluffy insulation in the ceiling, Mitre10 kitchen and a new bathroom.

What I did not realise at the time was the effect of the 21 chimneys, otherwise I’d never have done it. In winter, the wind was very obviously pushing and pulling through those holes, when the halogen lights were on and hot they were also going to be acting as venturis, pulling air up through themselves (I never proved this but it’s a good theory). Lastly, in summer the holes in the ceiling were very clearly a pathway for an enormous amount of heat, driving down through those same chimneys.

It was my first real lesson in building physics and how ‘hot to cold’ can work. We had terrible trouble with condensation in that brick and tile home — almost all of it forming on the timber and glass of an uninsulated sunroom that had no door to prevent moisture in the air from moving into that heat-sink. Thankfully, there was never a problem of condensation in the roof space — it was likely too warm and, with concrete tiles and no roof underlay, very drafty. All the moisture could easily escape.

If moisture can be prevented from leaking through ceilings (think every gap at the top of every wall behind scotia, every unsealed light fitting and every other hole you can see, the problem might not become a problem.

Above Sheathing Ventilation: Three Parts to the Roof-Side Fix

Which brings me to dedicated roof space ventilation. We are very aware of the current noise surrounding condensation in roof spaces. Let’s assume you’ve stopped the flow of air from internal spaces into the attic space. For the roof side of the equation, we do have a solution, with three aspects. One, create a ventilation pathway between cold cladding and the roof underlay.

We call it ‘ASV’ – Above Sheathing Ventilation. Sheathing here refers to the roof underlay, which could be loose-laid onto the top chord of the truss and/or a peel-and-stick roof underlay adhered to a plywood or OSB sheathing. This means air moves above the weathertightness layer, providing drying of moisture; water can drain freely down the weathertightness layer when condensation does occur on the underside of the cladding. The risk of moisture dripping onto the ceiling is avoided. Second, the roof underlay itself should be watertight to water droplets, but vapour-open to moisture. If you have not yet seen the speed this can occur through a TEEE membrane, you need to ask one of our regional sales team to show you.

Thirdly, and this is ‘unique’ to truss application, you could allow for some air movement from outside into the attic space and out again at the apex of the roof. Bear in mind, bringing in air from outside transports moisture too, because in the New Zealand climate air carries moisture. Always.

I mention truss roof as ‘unique’ because with a skillion roof there is no need for ventilation through the material assembly, provided a ventilation pathway is on the external side of the roof underlay (between cladding and underlay).

Airtightness First, Then Balanced Ventilation

Solution at the outside is still weather-dependent. 
Ventilation of attic space and ventilation through the ASV layer is dependent on wind pressure, therefore exposure (and conditions on the day), roof pitch, roof colour, ventilation percentage open area. It’s about as complex as buildings get, so I can understand why MRM state ‘ultimately… the responsibility lies with the designer’. I suggest it’s much easier to create deliberate airtightness, specify ventilation with a balanced-pressure heat recovery system (certainly not a positive pressure system unless you want to compound the problem), and then live comfortably with no condensation*.

For a more detailed explanation and solutions, see the article: Above Sheathing Ventilation Part 2: The Blue Planet.


*Reference:

Rallis, T. (2026, Winter). The increasing problem of condensation and how to manage it. Scope, (117).


Talk to Us About Roof Space Condensation Solutions

Maybe you’ve gone back to using ‘code-compliantaluminium windows without thermal breaks. These are a recipe for condensation and don’t meet Clause E3.

That is a story for another day, but get in touch if you’d like to learn more about these compliant, detailed, and practical solutions for avoiding roof space condensation.

Get Technical Support


Inadequate Airtightness and its Consequences

A thermally insulated, airtight building envelope plays a major role in determining how comfortable and pleasant an indoor environment is for us and how well we can work, learn or relax there. The air temperature has the strongest effect on our perception of comfort level: a temperature range of between 20 °C and 23 °C in homes is regarded as comfortable in winter, while temperatures of up to 26 °C are perceived as pleasant in summer. In this context, airtightness has a crucial influence on the effectiveness of thermal protection in both winter and summer.

Find out more about how you can achieve energy efficiency


Related Articles

 

Above Sheathing Ventilation – Part 1: Rise of the Cavity

Above-sheathing ventilation (ASV) uses solar energy to induce airflow between the cladding and the membrane by heating the roof cladding and warming the air in the cavity below.

more

 

Above Sheathing Ventilation – Part 2: The Blue Planet

Above Sheathing Ventilation (ASV) facilitates roof drying by using the same physics that creates rising clouds on the surface of the Earth.

more

 

Above Sheathing Ventilation – Part 3: Fighting the Sun

In Part 2 of this series, our brave new roof used Above Sheathing Ventilation (ASV) to battle the dark forces of winter. But summer brings another set of challenges.

more

 